Industrial UPS-UID Family
10-80kVA
UID Series UPS is an ture on-line double conversion UPS with input and output isolation transformers. It accordance with international safety standard such as IEC EN 62040-3 and provides high level power protection for control applications and harsh environments.
General Features
● Online double conversion
● Full DSP control
● High power factor
● Wide input adaptability
● Optimized battery management
● N+X parallel redundancy
● Strong overload capability
● Power walk in
● Generator mode
● Multi-protection
● EPO function
● User-friendly network management
Technical Specification
MODEL | UID10 | UID20 | UID30 | UID40 | UID60 | UID80 | ||
Capacity (VA/Watts) |
10kVA / 9kW | 20kVA / 18kW | 30kVA / 27kW | 40kVA / 36kW | 60kVA / 54kW | 80kVA/ 72kW | ||
INPUT | ||||||||
Operating voltage range |
380/400/415Vac (-25% / +20% ), (3Ph+N+PE) | |||||||
Operating frequency range |
50/60Hz(±5%) | |||||||
Power Factor | >0.97 (with filter) | |||||||
OUTPUT | ||||||||
Output Voltage | 380/400/415Vac (±1%) | |||||||
Output frequency | 50/60Hz (±0.05%) | |||||||
Harmonic Distortion (THDv) |
<3% with linear load | |||||||
Crest factor | 3:1 (max) | |||||||
Efficiency | ≥88% | ≥89% | ≥90% | ≥90.5% | ||||
BYPASS | ||||||||
Rated voltage | 380/400/415Vac | |||||||
Rated frequency | 50/60Hz | |||||||
Voltage protection range |
Upper limit: +20% (+10%,+15%,+20% adjustable)Lower limit: -40% (-10%, -20%, -30%, -40% adjustable) | |||||||
Frequency protection range |
±10% (±2.5%, ±5%,±10%, ±20% adjustable) | |||||||
BATTERY | ||||||||
Battery voltage | 384Vdc ( 360~384Vdc ) | |||||||
SYSTEM FEATURES | ||||||||
Transfer time | 0ms (Line mode →Battery mode) | |||||||
Overload | ≤110%/60min ,≤125%/10min ,≤150%/1min,to Bypass | |||||||
LED display | Input, Inverter, Bypass, Battery, Output, Status | |||||||
LCD display | I/O voltage, frequency, power, power factor, battery voltage, current, battery status, load percentage, UPS status, history record |
|||||||
Communication interface |
Dry contact, RS232, RS485, SNMP card (Optional) | |||||||
Optional | Harmonic filter, SNMP adapter, LBS cables, battery temperature sensor,Bypass current-sharing inductor | |||||||
ENVIRONMENT | ||||||||
Operating Temperature |
0℃~40℃ | |||||||
Storage temperature |
-25~55℃ | |||||||
Humidity range | 0~95% (non-condensing) | |||||||
Altitude | <1500m | |||||||
Noise level | <60dB | <65dB | ||||||
PHYSICAL | ||||||||
Dimension W×D×H (mm) |
350×650×1050 | 430×830×1100 | 720×690×1600 | |||||
Net weight (kg) | 148 | 163 | 230 | 255 | 386 | 426 | ||
Shipping weight (kg) |
168 | 183 | 263 | 288 | 432 | 472 | ||
STANDARDS | ||||||||
Safety | IEC/EN62040-1;IEC/EN60950-1 | |||||||
Performance | IEC 62040-3 | |||||||
EMC | IEC/EN62040-2;IEC61000-4-2;IEC61000-4-3;IEC61000-4-4; IEC61000-4-5;IEC61000-4-6;IEC61000-4-8;IEC 61000-4-11; |