Home >  OEM/ODM > OEM/ODM Services > ups> Online Transformerless UPS> YDC3300 10kVA-20kVA(UL/CSA Certificated)

YDC3300
10-20kVA
 
YDC3300 series UPS compliant with UL/CSA standards is aviable now! Equipped with three-level inverter topology, it results in high energy-saving and reliability. With higher power density, smaller footprint, it takes the leading position in the UPS industry with same power capacity; Adopting unique power unit redundancy design technology, decrease the abnormity risk of system after single-point failure, greatly increase the system reliability. For user, it is your best choice with high investment rate.

Features

·High power density design 
·N+Xparallel redundancy, maximum 4 units 
.Onlline double conversion with DSP contro 
.Cold start 
·Wide input voltage range:72~159Vac . 
·Multiple protection function:short-circuitoverload,overheat 



Technical Specification

MODEL YDC3310S/H YDC3315S/H YDC3320S/H
Capacity 10kVA / 10kW 15kVA / 15kW 20kVA / 20kW
INPUT
Nominal voltage 208/120Vac or 220/127Vac (3Ph+N+PE)
Operating voltage range 96~159Vac (Full load); 72~159Vac (50% load)
Operating frequency range 40~70Hz (50/60Hz Auto-Sensing)
Power factor 0.99
Bypass voltage range Max. voltage: 20% (Optional 10%, 15%, 20%) Min. voltage: 30% (Optional 10%, 20%, 30%)
Frequency protection range 50/60Hz±10%
ECO range Same as bypass
Harmonic distortion (THDi) 2% Non linear load
OUTPUT
Output voltage 208/120Vac or 220/127Vac (3Ph+N+PE)
Voltage regulation ±1%
Power factor 1
Output frequency Line mode ±1%/±2%/±4%/±5%/±10% of the rated frequency (Optional)
Bat.  mode 50/60 (±0.1%)Hz
  AC mode to Bat.mode 0ms
Transfer time Inverter to Bypass 0ms
Output waveform Pure Sinewave
   
Crest factor 3:01
Harmonic distortion (THDv) 1% Linear load
3% Non linear load
Overload AC mode 110%, last 60min; 125%, last 10min; 150%, last 1min;150% turn to bypass immediately
Bat.mode 110%, last 10min; 125%, last 1min; 150%, last 5s;150% shutdown UPS immediately
EFFICIENCY
Efficiency up to 94%
BATTERY
Battery voltage Standard unit ±120Vdc (20pcs 12V9AH) (2×20pcs 12V9AH,    
3×20pcs ±120Vdc (2×20pcs 12V9AH) ±120Vdc (3×20pcs 12V9AH)
 12V9AH optional) (3×20pcs 12V9AH optional)
Long run unit ±96 /±108 /±120 /±132 /±144Vdc
Charge Current Standard unit 1.35A (2.7/4.05A optional) 2.7A (4.05A optional) 4.05A
Long run unit 20A Max.
PHYSICAL
Dimension Standard unit 250×900×868mm
W×D×H Long run unit 250×580×655mm
Net weight 136kg/77kg 188kg/78kg 239kg/79kg
ENVIRONMENTAL
Operating temperature 040
Storage temperature -2555
Humidity range 095% (non-condensing)
Altitude <1500m, derating required when>1500m
Noise level 55dB 58dB
STANDARDS
Safety UL1778, CSA 22.2-107.3-14
EMC FCC Part 15 Subpart B, ANSI C63.4 2014
Energy star Energy star 2.0





Contact US Now